The GT200-HT-EI gateway enables seamless connectivity between HART devices and EtherNet/IP networks, with support for a wide range of PLCs and controllers including Rockwell, Omron, and ABB. This gateway can function as a replacement for 1756/1769 AI/AO HART modules, allowing users to continue to have access to a wealth of valuable instrument information while helping reduce cable clutter in the process.
-
Technical Specification
-
Order Information
-
Download
-
Selection Guide
-
Case Study
-
Related Products
-
Warranty & Service
Technical Specification:
Provides the best integration between Rockwell Automation PLCs and HART instruments.
- Supports one HART channel.
- HART can be used as a primary or secondary master.
- The HART interface supports point-to-point mode and multidrop mode.
- Under point-to-point mode, HART supports data burst operation.
- Ethernet 10/100M adaptive. Supports IP address conflict detection.
- Supports up to 127 commands. A HART output data buffer is up to 1000 bytes and a buffer of input data is up to 1600 bytes.
- Supports an internal or external HART sampling resistor.
- Supports at most 13 HART devices when using internal resistor (270Ω).
- Supports at most 15 HART devices when using external resistor (250Ω).
- Power supply: 24VDC (11V-30V), 90mA (24VDC).
- Operating Temp: -30°F to 158°F (-30°C to 70°C); Rel. Humidity: 5% to 95% (non-condensing).
- Dimension (W*H*D): 1 in*4 in*3.5 in (25mm*100mm*90mm).
- Mounting: DIN Rail Mounting (35mm).