Modbus TCP / BACnet IP Gateway

GT200-BM-MT
909-977-2988
WhatsApp

WhatsApp

+1-909-977-2988

The GT200-BM-MT gateway allows multiple Modbus TCP server/slave devices to be efficiently integrated into a BACnet/IP network, enabling seamless interoperability between Modbus TCP-based equipment and BACnet building automation systems including Johnson Controls, Honeywell, and Carrier.

BACnet/IP Features
  • Supports protocol conversion between Modbus TCP and BACnet/IP.
  • Modbus TCP and BACnet/IP share the same Ethernet interface for streamlined integration.
  • Dual Ethernet ports with self-adaptive capabilities, IP address conflict detection, and automatic routing for robust networking.
  • Supports BACnet/IP services: Who-Is, I-Am, Who-Has, I-Have, Read Property, Write Property, Read Property Multiple.
  • Supports up to:
    • 500 Binary Inputs (BI)
    • 300 Binary Outputs (BO)
    • 300 Binary Values (BV)
    • 500 Analog Inputs (AI)
    • 300 Analog Outputs (AO)
    • 300 Analog Values (AV)
    • 500 Multi-State Inputs (MSI)
    • 100 Multi-State Outputs (MSO)
Modbus TCP Features
  • Acts as a Modbus TCP client to communicate with up to 36 different IP addresses or Modbus TCP servers with different unit IDs.
  • Supports Modbus function codes: 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x0F, 0x10.
General
  • Power supply: 24VDC (range: 11–30VDC), 90mA @ 24VDC.
  • Operating temperature: -40°C to 70°C (-40°F to 158°F).
  • Humidity: 5% to 95% RH (non-condensing).
Physical Features
  • Dimension (W*H*D): 1.33 in * 4.56 in * 4.21 in (34 mm * 116 mm * 107 mm).
  • Mounting: 35mm DIN rail.
  • Protection rating: IP20.