PROFIBUS DP/EtherNet/IP Gateway

GT200-DPM-EI

V2.2

GT200-DPM-EI V2.2 Quick Start Guide

Product Appearance

Wiring

  • 1. Connect the gateway power interface to the power supply.
    Pin Function
    1 Power GND
    2 NC(Not Connected)
    3 24V+,DC Positive 24V
  • 2. Refer to wiring of the PROFIBUS DP interface.
    Pin Function
    3 PROFI_B, Data+
    5 GND
    8 PROFI_A, Data-
  • 3. 35mm DIN Rail Installation.

LED Status Indicators

Indicators of PROFIBUS DP:
Indicator Status Description
COM Green(Steady) ALL PROFIBUS DP Devices connected normally
Red(Steady) At least one PROFIBUS DP Device connection failure
OFF PROFIBUS DP master not configured
SYS Green(Steady) At least one PROFIBUS DP Device connected
Green(Blinking) PROFIBUS DP master configured,but no slave connection established
OFF No power or hardware fault

 

Indicators of EtherNet/IP:
Indicator Status Description
ES Red(blinking) IP address configuration in progress
Red DHCP mode
Green IP address started normally
NS Green EtherNet/IP connection established
Green(Blinking) EtherNet/IP connection not established

 

Indicators of Modbus TCP:
Indicator Status Description
ES Red(blinking) IP address configuration in progress
Red DHCP mode
Green IP address started normally
NS Green Modbus TCP connection established
Green(Blinking) Modbus TCP connection not established

Software Configuration

  • 1.Download SST-DPM-CFG software from www.sstautomation.com/Download1/ and install it.
  • 2.First, connect the gateway to the computer with an Ethernet cable. Use SST-DPM-CFG to build your configuration. The Ethernet supports two modes:Modbus TCP Server,EtherNet/IP Adapter.
  • 3. Configure the PROFIBUS DP parameters with SST-DPM-CFG software. After opening the software,you need to import the GSD file of the PROFIBUS DP device firstly and configure the device parameters through the GSD file,referring to chapter 6 of the manual.
  • 4. Then,the Ethernet end configures parameters such as IP and Modbus TCP function codes based on the application by choosing EtherNet/IP or Modbus TCP mode.Download the configuration by EtherNet cable.
For more information, please refer to the GT200-DPM-EI manual.

Communication Instructions

  • 1.After all configurations are downloaded, connect your PROFIBUS DP devices to the PROFIBUS DP interface of the gateway, and connect any Ethernet port of the gateway to the EtehrNet/IP Scanner or Modbus TCP Clinet.
  • 2.Observe the indicator lights to check the communication status.In normal communication, all four lights on the gateway are solid green.
For more information, please refer to the GT200-DPM-EI manual.