Universal Serial/PROFINET Gateway

GT200-PN-3RS

V6.0

GT200-PN-3RS V6.0 Quick Start Guide

Product Appearance

Wiring

  • 1. According to the gateway's power wiring label and 24V DC power wiring.
    Pin Function
    1 Power GND
    2 NC(Not Connected)
    3 24V+,DC Positive 24V
  • 2. Connect the Modbus serial device according to the gateway's serial port wiring label.
    Pin Function
    1 D+, RS485 Data Positive, connect to device D+
    2 D-, RS485 Data Negative, connect to device D-
    3 GND, connect to device GND
    Pin Function
    1 TX, RS232 Data Transmit, connect to device RX
    2 RX, RS232 Data Receive, connect to device TX
    3 GND, connect to device GND (Required for RS232)
  • 3. Connect the Gateway's to the computer with an Ethernet cable.
  • 4. Power on the gateway. Run the SST-TS-CFG software to configure the gateway.
  • 5. 35mm DIN Rail Installation.

LED Status Indicators

Indicators Status Description
PR
(Pull-up/down Resistor)
Solid Green Switch SW0 ON, 1K resistor
OFF Switch SW0 OFF, 47K resistor
Serial I Flashing Red Serial port is sending data
Flashing Green Serial port is receiving data
Serial II Flashing Red Serial port is sending data
Flashing Green Serial port is receiving data
Serial III Flashing Red Serial port is sending data
Flashing Green Serial port is receiving data
MS
(Module State)
See table below
NS
(Network State)
See table below

 

MS
(Module State)
NS
(Network State)
Description
OFF Flashing Red Start-up state, waiting to initialize
Solid Green Flashing Red Initialization complete, but no connection yet with PLC
Solid Green Solid Green PLC has connected
Other Other Undefined state

Software Configuration

  • 1. Download SST-TS-CFG software from www.sstautomation.com/Download1/ and install it.
  • 2. Download the GSDML file for GT200-PN-3RS from www.sstautomation.com/Download1/.
  • 3. Build your configuration using SST-TS-CFG and download it to the gateway. When the download is completed, the software will prompt to "whether to restart the gateway", click "Yes".
  • 4. Install the appropriate device description file in your PLC's PROFINET configuration tool.
  • 5. Configure the PROFINET network as required. Make sure that the configuration matches the configuration present in the GT200-PN-3RS. When GT200-PN-3RS establishes a connection with the PROFINET master, the gateway will display:
    MS: Solid Green, NS: Solid Green.
  • For more information, please refer to the GT200-PN-3RS manual.

Communication Instructions

  • 1. Connect your serial devices to the gateway’s serial interface. Depending on the product variant, the gateway features either three RS485 interfaces (GT200-PN-3RS485) or three RS232 interfaces (GT200-PN-3RS232).
    Please refer to the gateway manual for more details about specific connection methods.
  • 2. Observe the indicator lights to check the communication status.
    (use the debug feature in SST-TS-CFG to view live serial data).