• Technical Specification
  • Download
  • Selection Guide
  • Case Study

Technical Specification:

1.    Acts as PROFIBUS DP slave on PROFIBUS DP network, automatic baud rate detection on PROFIBUS DP(9600bit/s~12Mbit/s).

2.    1KV galvanic isolated on PROFIBUS DP interface.

3.    Supports ODVA standard EtherNet/IP communication protocol.

4.    EtherNet/IP supports three groups I/O connection at the same time.

5.    EtherNet/IP supports both reading and writing I/O data.

6.    Supports monitoring the other network connection status.

7.    Supports byte swapping: no swapping, double-byte swapping and four-byte swapping.

8.    Operating Temp:-40°F to 158°F(-40ºC to 70ºC).

9.    Rel Humidity: 5%-95% RH non-condensing.

10.   Dimension(W*H*D):40mm*125mm*110mm(1.6in*4.9in*4.5in).

11.   Mounting: DIN Rail Mounting(35mm).